THE GOVERNMENT
------------
SOCIALIST REPUBLIC OF VIET NAM
Independence - Freedom – Happiness
--------------
No. 118/2004/ND-CP
Hanoi, May 10, 2004
 
DECREE
AMENDING AND SUPPLEMENTING A NUMBER OF ARTICLES OF THE GOVERN-MENT'S DECREE NO. 54/1999/ND-CP OF JULY 8, 1999 ON PROTECTION OF SAFETY OF HIGH-VOLTAGE POWER GRIDS
THE GOVERNMENT
Pursuant to the December 25, 2001 Law on Organization of the Government;
At the proposal of the Minister of Industry,
DECREES:
Article 1.- To amend and supplement a number of articles of the Government's Decree No. 54/1999/ND-CP of July 8, 1999 on protection of safety of high-voltage power grids as follows:
1. To amend and supplement Point c, Clause 1 of Article 6 as follows:
"c/ The height is calculated from the bottom of the post base to the post top plus a vertical safety distance prescribed in the following table:

>> See also:  DECREE No.107/2009/ND-CP ON TRADING OF LIQUEFIED PETROLEUM GAS THE GOVERNMENT

Voltage (kV)
Up to 35
66 to 110
220
500
Distance (m)
2.0
3.0
4.0
6.0
2. To amend and supplement Article 7 as follows:
"Article 7.-
1. With regard to trees and plants in the safety protection corridors of high-voltage power grids:
a/ In cities, provincial towns and district townships:
The distance from the highest point of trees to the transmission line of a voltage of up to 35 kV in the static position must not be shorter than the distance prescribed in the following table:
Voltage (kV)
Up to 35
Distance (m)
Insulated wire
Bare wire
 
0.7
1.5
The vertical distance from the highest point of trees to the transmission line of a voltage of between 66 kV and 500 kV in the static position must not be shorter than the distance prescribed in the following table:
Voltage (kV)
66 to 110
220
500
Distance (m)
Bare wire
 
2.0
2.5
4.0
b/ Outside cities, provincial towns or district townships:

>> See also:  How to establish a foreign-invested company in Vietnam?

The vertical distance from the highest points of trees to the transmission lines in the static position must not be shorter than the distance prescribed in the following table:
Voltage (kV)
Up to 35
66 to 110
220
500
Distance (m)
Insulated wire
Bare wire
Bare wire
 
0.7
2.0
3.0
4.0
6.0
 